DataSheet.es    


PDF BE5982 Data sheet ( Hoja de datos )

Número de pieza BE5982
Descripción Emergency Stop Module
Fabricantes ETC 
Logotipo ETC Logotipo



Hay una vista previa y un enlace de descarga de BE5982 (archivo pdf) en la parte inferior de esta página.


Total 2 Páginas

No Preview Available ! BE5982 Hoja de datos, Descripción, Manual

Safety technique
Emergency stop module BE 5982
safemaster
· According to EU Directive for machines 98/37/EG
· According to EN 60 204-1, DIN VDE 0113 part 1 (11.98)
· Safety category 4 according to DIN EN 954-1
· Output: 2 NO contacts for AC 250 V
· Single-channel emergency stop circuit
· LED indication for channels 1 / 2 and operating state
· Short circuit protection
· Wire connection: also 2 x 1,5 mm2 stranded ferruled (isolated),
DIN 46 228-4 or
2 x 2,5 mm2 stranded ferruled DIN 46 228-1/-2/-3
· Width 22,5 mm
www.DataSheet4U.com
Function diagram
Approvals and marking
Pushbutton
On
Emergency
stop (Off)
K1
K2
M7218
Block diagram
A1(+)
Y1 Y2
PTC
K1
K2
K1
K2
Mains K1/K2 K1
K2
13 23
K1
K2
A2(-)
M6760_a
Circuit diagram
A1 13 23 24
A1 Y1
13
K1
K2
A2 Y2
14
14 Y1 Y2 A2
23
24
M7384_a
14 24
ET
Application
· Protection of persons and machines
· Emergency stop circuits on machines
Indication
LED power supply:
LED K1/K2:
on when operating voltage present
on when output relays K1, K2 are
energized
Notes
When using the E-stop module with "automatic start" mode, the automatic
restart (according to EN 60 204-1 part 9.2.5.4.2 and 10.8.3) has to be
inhibited by the machine control.
Technical data
Input
Nominal voltage UN:
Voltage range
at 10 % residual ripple:
at 48 % residual ripple:
Nominal consumption:
Control voltage Y1:
Control current:
Recovery time:
DC 24 V
DC 0,9 ... 1,1 UN
DC 0,8 ... 1,1 UN
approx. 1,6 W
DC 24 V
typ. DC 45 mA
0,5 s
Output
Contacts
BE 5982.02:
Response time:
Release time:
Contact type:
Output rated voltage:
Thermal current Ith:
Switching capacity
to AC 15:
Electrical life
to AC 15 at 2 A, AC 230 V:
Permissible switching
frequency:
Short ciruit strength
max. fuse rating:
Mechanical life:
2 NO contacts
max. 100 ms
max. 35 ms
Relay, positively driven
AC 250 V
see continuous limit curve
(max. 6 A in one contact path)
5 A / AC 230 V
for NO contact
2 A / AC 230 V
for NC contact
EN 60 947-5-1
EN 60 947-5-1
105 switching cycles EN 60 947-5-1
600 switching cycles / h
4 A gL
EN 60 947-5-1
10 x 106 switching cyles
All technical data in this list relate to the state at the moment of edition. We reserve the right
for technical improvements and changes at any time.
1
BE 5982 / 30.10.01 d

1 page





PáginasTotal 2 Páginas
PDF Descargar[ Datasheet BE5982.PDF ]




Hoja de datos destacado

Número de piezaDescripciónFabricantes
BE5982Emergency Stop ModuleETC
ETC
BE5982.02Emergency Stop RelayETC
ETC

Número de piezaDescripciónFabricantes
SLA6805M

High Voltage 3 phase Motor Driver IC.

Sanken
Sanken
SDC1742

12- and 14-Bit Hybrid Synchro / Resolver-to-Digital Converters.

Analog Devices
Analog Devices


DataSheet.es es una pagina web que funciona como un repositorio de manuales o hoja de datos de muchos de los productos más populares,
permitiéndote verlos en linea o descargarlos en PDF.


DataSheet.es    |   2020   |  Privacy Policy  |  Contacto  |  Buscar