HX03-P PDF даташит
Спецификация HX03-P изготовлена «LEM» и имеет функцию, называемую «(HX02-P - HX06-P) Current Transducer». |
|
Детали детали
Номер произв | HX03-P |
Описание | (HX02-P - HX06-P) Current Transducer |
Производители | LEM |
логотип |
2 Pages
No Preview Available ! |
Current Transducer HX 02..06-P
IPN = 2 .. 6 A
For the electronic measurement of currents: DC, AC, pulsed, mixed,
with a galvanic isolation between the primary circuit (high power) and
the secondary circuit (electronic circuit).
Electrical data
Primary nominal Primary current
r.m.s. current measuring range
I
PN
(A)
I
P
(A)
2 ±6
3 ±9
4 ±12
6 ±18
Primary Conductor
Diameter x Turns
(mm)
0.5d x 30T
0.6d x 20T
0.7d x 15T
1.0d x 10T
Type
HX 02-P
HX 03-P
HX 04-P
HX 06-P
V
OUT
ROUT
R
L
VC
I
C
Vd
V
e
www.DataSheet4U.com
Output
voltage
@
±
I,
PN
R
L
=
10
kΩ,
T
A
=
25°C
Output impedance
Load resistance
Supply voltage (± 5 %)1)
Current consumption
R.m.s. voltage for AC isolation test, 50/60Hz, 1 mn
R.m.s. voltage for partial discharge extinction
at 10pC
Impulse withstand voltage, 1.2/50µs
±4
< 50
≥ 10
± 15
< ± 15
>3
≥1
≥6
V
Ω
kΩ
V
mA
kV
kV
kV
Accuracy-Dynamic performance data
X
εL
VOE
VOH
εVOT
TC G
tr
f
Accuracy @ IPN, TA = 25°C (without offset)
Linearity error (0 .. ± IPN)
Electrical offset voltage, TA = 25°C
Hysteresis offset voltage @ IP = 0;
after an excursion of 3 x IPN
Thermal drift of VOE
Thermal drift of the gain (% of reading)
Response time @ 90% of IP
Frequency bandwidth (-3 dB) 2)
< ± 1 % of IPN
< ± 1 % of IPN
< ± 40
mV
< ± 15
max. ± 1.5
± 0.1
≤3
50
mV
mV/K
%/K
µs
kHz
General data
TA Ambient operating temperature
TS Ambient storage temperature
m Mass
Min. internal creepage distance/clearance
Isolation material group
Standards
- 25 .. + 85 °C
- 25 .. + 85 °C
8g
≥ 5.5
mm
I
EN50178
Features
• Galvanic isolation between primary
and secondary circuit
• Hall effect measuring principle
• Isolation voltage 3000V
• Low power consumption
• Extended measuring range 3x IPN
• Power supply from ±12V to ±15V
• Material according to UL94-V0
Advantages
• Low insertion losses
• Easy to mount with automatic
handling system
• Small size and space saving
• Only one design for wide current
ratings range
• High immunity to external
interference.
Applications
• Switched Mode Power Supplies
(SMPS)
• AC variable speed drives
• Uninterruptible Power Supplies
(UPS)
• Electrical appliances
• Battery supplied applications
• DC motor drives
Application Domain
• Industrial
Notes : 1) Also operate at ±12V power supplies, measuring range reduced to ±2.5x IPN
2) Small signal only to avoid excessive heating of the magnetic cores
060920/1
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
Page 1/2
www.lem.com
No Preview Available ! |
Dimensions HX 02..06-P (in mm. 1 mm = 0.0394 inch)
HXHHXX00023.2..0..62.-25P-5P-P
19 Max.
HXHX5500-PP
Terminal Pin Identification
19 Max.
1 ..... -15 V
2 ..... 0 V
3 ..... +15 V
4 ..... Output
5 ..... Primary input Current (+)
6 ..... Primary input Current (-)
3 10.85
d
4 OUT
3 +V
20
1 -V or 0
6
5
3 10.85
Terminal Pin Identification
1.....-15V
2.....0V
3.....+15V
4.....Output
5.....Primary input Current(+)
6.....Primary input Current(-)
Primary conductor diameter
3 8.8
5.4
HX 02-P
03-P
04-P
d 0.56 0.6 0.7
06-P
1.0
4 OUT
65
3S+eVcondary pins dimension
20.05 x 0.25
1 -V or 0
1.2
3 8.8
5.4
Top view
HHXX 0025--PP
41123
Lot No.
Primary conductor diameter / dimension
Safety
HX 03-P 05-P 10-P 15-P 20-P 25-P 50-P
d 0.6 0.8 1.1 1.4 1.6 1.6 1.2x6.3
SecondarTyhpisinstradinmsednuscioenr must be used in electric/electronic equipment
0.5x0w.2i5th respect to applicable standards and safety requirements
in accordance with the following manufacturer's operating
instructions.
Caution, risk of electrical shock
When operating the transducer, certain parts of the module can
carry hazardous voltage (eg. primary busbar, power supply).
Ignoring this warning can lead to injury and/or cause serious
damage.
This transducer is a built-in device, whose conducting parts
must be inaccessible after installation.
A protective housing or additional shield could be used.
Main supply must be able to be disconnected.
060920/1
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
Page 2/2
www.lem.com
Скачать PDF:
[ HX03-P.PDF Даташит ]
Номер в каталоге | Описание | Производители |
HX03-P | Current Transducer HX 03~50-P | LEM |
HX03-P | (HX02-P - HX06-P) Current Transducer | LEM |
Номер в каталоге | Описание | Производители |
TL431 | 100 мА, регулируемый прецизионный шунтирующий регулятор |
Unisonic Technologies |
IRF840 | 8 А, 500 В, N-канальный МОП-транзистор |
Vishay |
LM317 | Линейный стабилизатор напряжения, 1,5 А |
STMicroelectronics |
DataSheet26.com | 2020 | Контакты | Поиск |